Performance:
• With double conversion online design, zero output transfer time.
• Adopt DSP digital control, excellent performance indicators, more steady and reliable.
• Adopt active power factor correction technology (PFC), the input power factor is 1, can reduced the pollution to the grid, to energy saving and reducing system investment cost.
• Output voltage 208Vac/220Vac/230Vac/240Vac can be set.
• Ultra-wide input voltage range , input voltages available 110V instead of turn to battery power.
• With LCD+LED real-time display, UPS operating available for Detection.
• With self-detection function, can detect hidden faults of UPS.
• Cold start by battery without grid Input.
• Input frequency range 40~70Hz, support various fuel generators.
• With AC input over voltage, low voltage protection, output overload protection, short circuit protection, temperature protection, battery low voltage warning protectionand battery overcharge protection.
• Output power factor 1.0 for your option. max efficiency reach 95%, reduce loss of UPS.
• Standard RS232 communication outlet ,connect UPS and computer to realize multifunctional and multi-purpose monitoring and management operations, available SNMP card (optional) to UPS remote monitoring function
• The split type model can directly replace the entire built-in battery pack, avoiding safety accidents caused by battery replacement.
Specification:
MODEL | EH55 6KS | EH55 6K Split Type | EH55 10KS | EH55 10K Split Type |
---|---|---|---|---|
Rated Capacity | 6KVA/6KW | 10KVA/10KW | ||
Input | ||||
Input format | L+N+PE | |||
Rated input voltage | 208/220/230/240VAC | |||
Voltage range | 110~300VAC | |||
Frequency range | 50/60±6Hz (Default), ±10Hz (Settable) | |||
Input power factor | ≥0.99 | |||
Input total harmonic distortion | ≤4% inear load; ≤6% non-linear load (PF=0.7) | |||
Outputm | ||||
Output format | L+N+PE | |||
Output voltage | 208/220/230/240VAC | |||
Output accuracy | ±1% | |||
Output frequency | For on-line mode: follow current frequency, battery mode: 50 / 60Hz±0.1% | |||
Output harmonic distortion | ≤ 2% linear load; ≤ 4% nonlinear load (PF=0.7) | |||
Overload capacity | AC Mode:
30min@102%~110% Load; 10min@110%~130% Load; 30s@130%~150% Load; 200ms@>150% Load Battery Mode: 10min@102%~110% Load; 1min@110%~130% Load; 10s@130%~150% Load; 200ms@>150% Load |
|||
Switching time | ||||
Switch to battery mode | 0ms | |||
Switch to bypass | 4ms | |||
AC priority mode | Support | |||
Efficiency | ||||
AC Mode (Full Load) | Peak efficiency 95.5%, Full load efficiency 95% | |||
Battery Mode (Full Load) | Peak efficiency 95.3%, Full load efficiency 94.8% (20pcs Battery) | |||
Battery | ||||
Battery type | Lead Acid Battery | |||
Battery number | 16/18/20 (adjustable) 16 (default ) | 7Ah*16 | 16/18/20 (adjustable) 16 (default ) | 9Ah*16 |
Chaging current | 1-12A (adjustable) | 1A (default) | 1-12A (adjustable) | 1A (adjustable) |
Inside batteries | / | Separable | / | Separable |
Charging mode | Two-stage/three-stage charging | |||
Display | ||||
LCD | 2×8 PIN/Pitch 2.54mm, support 128-bit segment code, up to 4 buttons + 4 LEDs, can display operating mode / load / input / output, etc. | |||
Interface | ||||
RS-232 | Support: Windows 2000/2003/XP/Vista/2008/7/Linux/Unix and MAC | |||
USB | Windows Family & MAC | |||
EPO | Support | |||
Intelligent slot (Optional) | SNMP/AS400 Relay Card/RS485 | |||
Maintenance bypass switch (Optional) | Support | |||
Environmental parameters | ||||
Operating ambient temperature | 0~40℃ | |||
Operating environment humidity | 20%~95%(no condensation) | |||
Storage temperature | -15~60℃ (batteries: 0~40℃ ) | |||
Altitude | The elevation should not exceed 1000m, 1000m or above, up to 4000 m, reference IEC62040 | |||
Noise | ≤50db | |||
Mechanical Specifications | ||||
Dimensions (D*W*H) (mm) | 460*200*360 | 460*200*700 | 460*200*360 | 460*200*770 |
Net weight (kg) | 13 | 62 | 13 | 64 |