EH9335 Pro Series High Frequency Three Phase (3/3) Online UPS (20-80KVA)
The EH9335 Pro series UPS is three-in, three-out/three-in single-out. The product capacity covers all power segments from 20kVA to 80kVA, which is convenient for users to configure flexibly. This series of UPS can solve almost all power problems, such as power outage, city power high voltage, city power low voltage, voltage drop, amplitude reduction, Power problems such as high voltage pulses, voltage fluctuations, surge voltages, harmonic distortion, clutter interference, and frequency fluctuations.
ContactFeatures:
(1) Three in three out / three in single out UPSThe series is a three-in and three-out UPS. The input current is three-phase balanced, which can equalize the load of the three-phase power grid; the output can be changed to single-phase output.
(2) Digital controlAll parts of the UPS are digitally controlled. The UPS has excellent performance indicators, high system stability, self-protection and fault diagnosis capabilities, and avoids the risk of analog device failure, making the control system more stable and reliable.
(3) The number of external batteries is optional (±16/18/20 sections are optional)The number of external batteries for this series of UPS can be selected according to the user’s needs: ±16/18/20 knots.
(4) Charging current can be setThis series of UPS automatically assigns a reasonable charge current by setting the user-configured battery capacity. Constant voltage charging mode, constant current charging mode and floating charging mode can automatically and smoothly switch.
(5) Intelligent monitoring functionThis series of UPS can realize remote monitoring of UPS when an optional SNMP card is selected.
(6) Smart charging methodThis series of UPS uses an advanced two-stage three-stage charging method.The first stage is high constant current charging, quickly recharge about 90% of the power; the second stage of constant voltage charging, can activate the battery characteristics and fully charge the battery; the third stage is floating charge mode.This can balance the goal of fast charging and extending battery life, saving users’ battery investment.
(7) LCD displayThis series of UPS uses LCD and LED dual display, which allows users to more intuitively understand the working status and operating parameters of the UPS such as input/output voltage and frequency load capacity, battery capacity and internal temperature, so that all operations can be seen at a glance
(8) EPO FunctionAn emergency shutdown (EPO) button is embedded on the UPS unit panel,user can externally connect the EPO button. Press the EPO button in an emergency to shut down urgently; and have a remote emergency shutdown (REPO) function.
Application:
The EH9335 series is the best choice for data centers, network management centers, and enterprise server rooms in various industries or fields such as telecommunications, finance, transportation, government,manufacturing, and energy.
Model | EH9335-20KS | EH9335-30KS | EH9335-40KS | EH9335-60KS | EH9335-80KS | |
---|---|---|---|---|---|---|
Power | 20KVA /18KW | 30KVA /27KW | 40KVA /32KW | 60KVA /54KW | 80KVA /64KW | |
Input | ||||||
Input | Three-phase four-line + ground | |||||
Rated Power | 380/400/415Vac | |||||
Voltage Range | 208~478Vac | |||||
Frequency Range | 45-55Hz at 50Hz/54-66Hz at 60Hz (Auto sensing) | |||||
Power Factor | ≥ 0.99 | |||||
Input Current Harmonic | ≤ 3%(100% Nonlinear load ) | |||||
Bypass Range | Bypass protection voltage upper limit:220V:+ 25%(Optional+ 10%,+ 15%,+ 20%); 230V:+ 20%(Optional+ 10%,+15%); 240V:+ 15% (Optional+10%) | |||||
Bypass protection voltage lower limit:-45%(Optional -20%,-30%) | ||||||
Bypass frequency protection range:±10% | ||||||
Output | ||||||
Output | Three-phase four-line + ground or single phase+N | |||||
Rated Voltage | 380/400/415Vac or 220/230/240Vac | |||||
Voltage accuracy | ±1% | |||||
Output Frequency | Utility Mode | Synchronous with input; when the mains frequency exceeds ±10% maximum (±1%, ±2%, ±4%,±5% can be set), the output frequency is 50*(±0.2)Hz | ||||
Battery Mode | (50/60±0.2%)Hz | |||||
Load Peak Ratio | 3:1 | |||||
Output Voltage Distortion | ≤ 2% Linear Load ≤ 5% Nonlinear Load | |||||
Battery | ||||||
Efficiency | Normal Mode≥ 94.5% | |||||
Battery Voltage | Optional :±192V±216V±240V DC (±16/18/20 P CS) | |||||
Charging Current | 10A max | |||||
Transfer time | Utility mode to bypass mode: 0ms (tracking); utility mode to battery mode: 0ms | |||||
Protection | ||||||
Overload Capability | Normal Mode | Load ≤ 110%, 10mins, ≤ 125%, maintain 1mins, ≥ 150% shut down immediately. | ||||
Over Temperature Protection | Normal mode : Switch to bypass mode; Battery mode : Turn off the output immediately. | |||||
Emergency shutdown (EPO) | Turn off the output immediately | |||||
Operating Environment | ||||||
Communication Connection | USB, RS485, dry contact, parallel (optional), SNMP card (optional), relay card (optional) | |||||
Working Temperature | 0℃~ 40℃ | |||||
Storage Temperature | -25℃~ 55℃ | |||||
Relative Humidity | 0 ~ 95% No condensation | |||||
Altitude | < 1500m, when above 1500m, derate according to GB/T 3859.2 | |||||
Physical characteristics | ||||||
Size (D*W*H) | 724*250*734mm | 805*335*978mm | ||||
Net Weight(kg) | 45 | 46 | 48 | 80.5 | 82.5 | |
Executive standard | YD/T1095-2008 |